Dwyer Series EDA Electronic Pressure Controller

Features & Benefits

  • Display Units: psi, kg/cm², bar, in Hg, ft w.c., kPa, MPa, %FS, in w.c., mbar, cm w.c., mm Hg, or oz/in² (choices depend on range).
  • Test Mode: Simulates input over the range without pressuring to easily test switches and transmitter output feature.
  • Failsafe: For sensor failure, over pressure, high temperature limit, low temperature limit, or keypad short. User chooses if relay is de-energized, energized, or no action. With transmitter option, user chooses an output of 3.6 mA 22 mA, or no action.
  • Alternation: Selectable alternation of set points between the relays for even wear on duplex pump applications.

Specifications

Service: Compatible liquids and gases.

Wetted Materials: 316L SS.

Housing: Glass filled plastic.

Accuracy: ±1% of F.S. including linearity, hysteresis, and repeatability (indicator and transmitter).

Stability: < ±2% of F.S. per year.

Pressure Limits: Ranges up to 6,000 psi: 1.5 x range; 8,000 psi range: 10,000 psi.

Temperature Limits: Ambient: 20 to 140°F (-6.6 to 60°C); Process: 0 to 176°F (-18 to 80°C).

Compensated Temperature Limits: 32 to 122°F (0 to 50°C).

Thermal Effect: ±0.05% of F.S./°F.

Display: 4-digit backlit LCD (Digits: 0.60″H x 0.33″W).

Power Requirements: 12 to 30 VDC/AC.

Power Consumption: 2.5 watts.

Electrical Connections: Removable terminal blocks with two 1/2″ female NPT conduit connections.

Enclosure Rating: Meets NEMA 4X (IP65).

Warm Up Time: <10 seconds.

Mounting Orientation: Any position.

Weight: 1.18 lbs (535 g).

Agency Approvals: CE and UL.

SWITCH SPECIFICATIONS:

Switch Type: 2 SPDT relays.

Electrical Rating: 5 A @ 120/240VAC, 1 A @ 30 VDC.

Repeatability: ±1% of FS (switching only).

Set Points: Adjustable 0-100% of FS.

Switch Indication: External LED for each relay on the front panel.

Switch Reset: Manual or Automatic.

 

Transmitter specifications

Output Signal: 4-20 mA, 1-6 VDC, 1-5 VDC, 0-5 VDC, or 0-10 VDC (direct or reverse output selection).

Minimum Excitation: 14 VDC.

Zero and Span Adjustments: Menu scalable within the range.