DESCRIPTION
The device T has built in self test, survey of the connected sensors and the complete alarm processing – accordingly to approval guidelines for overfill sensors (ZG-ÜS).
Note: The function test with the external push button does not replace the annual operation test, which is specified in the German specifications DIBt-ZG-ÜS § 6.2.
TECHNICAL FEATURES
- Supply power: 230 V AC ±10% 50/60 Hz
- Power consumption: approx. 6 VA / 6 W max.
- Ambient temperature: -20 to +60° C
- Housing: protection: IP 65 (acc. EN 60 529)
- 200 x 205 x depth= 100 mm
- Sensor supply power: 15 V DC, short circuit proof
- Input: max. 4 sensors
- 1 external reset contact
- Outputs: 4 floating changeover contacts (1 contact per sensor)
- 1 floating changeover contact for group alarm
- 1 floating changeover contact for external horn
- Contact rating: 250 V AC / 115 V DC – 500 VA / 3 A
- Indication: Red blinking = not acknowledged alarm
- Red steady burning = acknowledged alarm
- Yellow blinking = sensor malfunction
- Yellow steady burning = test is running
- Green steady burning = sensor in operation
- Green LED Off = no sensor connected
- 1x piezo – signalization horn >75 dB (A)/1m
- 1x extra bright flash LED for sum. alarm
- Control elements: reset push button for alarm acknowledgement
- Push button for system test
- CE Mark: in accordance with low voltage directive (73/23/CEE) and EMC directives (89/336/CEE)