Dwyer Series 605

Please see SERIES AT2605 for ATEX approved.

Features & Benefits

  • Monitor pressures in ducts, rooms, or total building pressures.
  • Filter monitoring.
  • Local indication of clean room pressures with process signal sent to control room.

Specifications

Gage specifications

Service: Air and non-combustible, compatible gases.
Wetted Materials: Consult factory.
Accuracy: See Ordering page.
Stability: ±1% F.S./yr.
Pressure Limits: See Ordering page.
Temperature Limits: 20 to 120°F (-6.67 to 48.9°C).
Process Connections: 1/8″ female NPT.
Size: 4″ (101.6 mm) dial face, 5″ (127 mm) O.D. x 2-11/16″ (68.3 mm).
Weight: 1 lb, 12.6 oz (811 g).
Agency Approvals: CE.

 

Transmitter specifications

Accuracy: See Ordering page (includes linearity, hysteresis, repeatability).
Temperature Limits: 20 to 120°F(-6.67 to 48.9°C).
Compensated Temperature Range: 32 to 120°F (0 to 48.9°C).
Thermal Effect: ±0.025% F.S./°F (0.045% F.S./°C).
Power Requirements: 10-35 VDC (2-wire).
Output Signal: 4 to 20 mA.
Zero and Span Adjustments: Protected potentiometers.
Loop Resistance: DC; 0-1250 ohms maximum.
Current Consumption: DC; 38 mA maximum.
Electrical Connections: Screw terminal block.
Mounting Orientation: Diaphragm in vertical position. Consult factory for other position orientations.